User ManualADAM-6200 SeriesIntelligent Ethernet I/O Module
ADAM-6200 User Manual 4 Group ConfigurationIn certain application scenarios, it’s necessary to set multiple modules with the samesettings because the
ADAM-6200 User Manual 94 Logic StageWhen you click the Logic stage icon, you should see a dialog window as below.For each logic rule, there will be a
95 ADAM-6200 User ManualChapter 4 System Configuration Execution StageWhen you click the Execution stage icon, you should see a dialog window as belo
ADAM-6200 User Manual 96Send to Next Rule (SendToNextRule)You can combine different logic rules into one single rule, which can help buildingmore comp
97 ADAM-6200 User ManualChapter 4 System Configuration Output StageWhen you click the Output stage icon, you will see a pop-up window as below. There
ADAM-6200 User Manual 98After you decide the target device, then you can choose the output action by theOperation Type combo box. The default setting
99 ADAM-6200 User ManualChapter 4 System ConfigurationCounter Channel Setting (DI_Counter)Below are the steps to configure counter channel setting:1.
ADAM-6200 User Manual 100Local or Remote Internal Flag (AuxFlag)You can assign the logic result value from the Execution stage, to local or remoteinte
101 ADAM-6200 User ManualChapter 4 System ConfigurationThe following table will show the logic true and false of output actions.Output ActionTrue acti
ADAM-6200 User Manual 102 Internal Flag for Logic Cascade and Feedback Logic CascadeUsing internal flag as interface, you can combine different logi
103 ADAM-6200 User ManualChapter 4 System ConfigurationRule 1.Rule 2.
5 ADAM-6200 User ManualChapter 1 Product Overview1.2.2 Integrated automation application with IT technologies Remote Monitoring and Control with Smar
ADAM-6200 User Manual 104Rule 3.We use the logic rule 1 to check if AI channel 0 value of the ADAM-6217 is within 3 ~5 Volt. Logic rule 2 is used to c
105 ADAM-6200 User ManualChapter 4 System ConfigurationDistributed Logic CascadeLogic Cascade function is not limited on one single module. Since you
ADAM-6200 User Manual 106Rule 2.Rule 3.Using Local or Distributed Logic Cascade architecture, there will be no limitation forinput numbers of logic ru
107 ADAM-6200 User ManualChapter 4 System ConfigurationFeedbackWhen you choose the same internal flag for the input condition and output of one sin-gl
ADAM-6200 User Manual 108GCL Rule Execution SequenceThere are 16 logic rules on one ADAM-6200 module. As below, you can see the exe-cution flow for on
109 ADAM-6200 User ManualChapter 4 System ConfigurationGCL Execution and Data Transfer Performance1. Local OutputCondition: Running 1 logic rule on on
ADAM-6200 User Manual 110Now, we can use GCL logic to achieve the same control operation. Two logic rulesare used. The complete logic architecture is
111 ADAM-6200 User ManualChapter 4 System ConfigurationIn the example project, DI 0 is used as a trigger to start the sequential control action.Theref
ADAM-6200 User Manual 112You can simply implement one AND logic operator to achieve this control system.However, since one logic rule only has three i
113 ADAM-6200 User ManualChapter 4 System Configurationin logic rule 2, so DO 0 will change every 0.5 second. The GCL logic rule architectureis shown
ADAM-6200 User Manual 61.3 ADAM-6200 Series FamilyCategory Model DescriptionAnalog I/OADAM-6217 8-ch Isolated Analog Input Modbus TCP ModuleADAM-6224
ADAM-6200 User Manual 114You can see that DO 0 will only be triggered when rising edge of DI 0 occurs. In theexample project we provide, the DO status
115 ADAM-6200 User ManualChapter 4 System Configuration7. Falling EdgeFor Falling Edge application, the DO value will be activated to logic high, when
ADAM-6200 User Manual 116When you use GCL to achieve falling edge application, 3 logic rules, 1 Internal Timer(Timer 0) and 1 Internal Flag (Flag 0) a
117 ADAM-6200 User ManualChapter 4 System ConfigurationIn order to implement this kind of application, 9 logic rules, 1 Internal Counter (Coun-ter 0)
ADAM-6200 User Manual 1189. DI Event Trigger (Only Occurs Once)We can simply use GCL to perform Event trigger. For this kind of application, a DIchann
119 ADAM-6200 User ManualChapter 4 System Configuration4.3.6 Remotely Monitoring and Control via Web ServerAs mentioned in feature highlight section,
ADAM-6200 User Manual 1203. Enter the account and password.Note! The default setting of account is "root", and password is "00000000&qu
121 ADAM-6200 User ManualChapter 4 System Configuration4. Click Login button, you will see the operation page. In this page, you will not only to moni
ADAM-6200 User Manual 122
Appendix AA I/O Modbus Mapping Table
7 ADAM-6200 User ManualChapter 1 Product Overview1.4 Mechanical Design and Dimensions Front View Bottom Vie
ADAM-6200 User Manual 124A.1 I/O Modbus Mapping TableA.1.1 Modbus Function Code IntroductionTo full-fill the programming requirement, there is a serie
125 ADAM-6200 User ManualAppendix A I/O Modbus Mapping TableAddress (4X):00121 0 Open-Circuit Flag (Burnout)Read00122 1 Read00123 2 Read00124 3 Read0
ADAM-6200 User Manual 12640011 0 Historical Max. AI ValueRead40012 1 Read40013 2 Read40014 3 Read40015 4 Read40016 5 Read40017 6 Read40018 7 Read4001
127 ADAM-6200 User ManualAppendix A I/O Modbus Mapping TableNote:1. Users can configure the High alarm value in the ADAM.NET utility. When AI value is
ADAM-6200 User Manual 128Note:1. The value definition of DI Event Status2. The value definition of AO StatusFirst registerSecond register40111 0 DI E
129 ADAM-6200 User ManualAppendix A I/O Modbus Mapping Table3. Type Code TableA.1.4 ADAM-6250 15-ch Digital Input/Output ModuleAddress (0X):Input Rang
ADAM-6200 User Manual 130Address (4X):00049 0 Clear OverflowR/W00050 1 R/W00051 2 R/W00052 3 R/W00053 4 R/W00054 5 R/W00055 6 R/W00056 7 R/W00057 0
131 ADAM-6200 User ManualAppendix A I/O Modbus Mapping Table40045 – 40046 0 Set Absolute PulseR/W40047 – 40048 1 R/W40049 – 40050 2 R/W40051 – 40052
ADAM-6200 User Manual 132A.1.5 ADAM-6251 16-ch Digital Input ModuleAddress (0X):Address (0X) Channel Description Attribute00001 0 DI ValueRead00002
133 ADAM-6200 User ManualAppendix A I/O Modbus Mapping Table00049 0 Counter Start (1) / Stop (0)Write00050 1 Write00051 2 Write00052 3 Write00053 4 W
ADAM-6200 User Manual 81.5 SwitchIt’s non-functional now, but reserved for future use.1.6 LED DefinitionLED Color Indication BehaviorStatus/ComGreen(S
ADAM-6200 User Manual 134Address (4X):00081 0 DI Latch StatusR/W00082 1 R/W00083 2 R/W00084 3 R/W00085 4 R/W00086 5 R/W00087 6 R/W00088 7 R/W00089 8
135 ADAM-6200 User ManualAppendix A I/O Modbus Mapping TableA.1.6 ADAM-6256 16-ch Digital Output ModuleAddress (0X):Address (4X):Address (0X) Channel
ADAM-6200 User Manual 13640033 – 40034 0 Pulse Output High Level WidthR/W40035 – 40036 1 R/W40037 – 40038 2 R/W40039 – 40040 3 R/W40041 – 40042 4 R/W
137 ADAM-6200 User ManualAppendix A I/O Modbus Mapping Table40097 – 40098 0 Set Incremental PulseR/W40099 – 40100 1 R/W40101 – 40102 2 R/W40103 – 401
ADAM-6200 User Manual 138A.1.7 ADAM-6260 6-ch Relay Output ModuleAddress (0X):Address (4X):Address (0X) Channel Description Attribute00017 0 DO Val
139 ADAM-6200 User ManualAppendix A I/O Modbus Mapping TableA.1.8 ADAM-6266 4-ch Relay Output Module with 4-ch DIAddress (0X):Address (0X) Channel D
ADAM-6200 User Manual 140Address (4X):Address (4X) Channel Description Attribute40001 – 40002 0 Counter/Frequency ValueRead40003 – 40004 1 Read4000
Appendix BB ADAM-6200 ASCII Commands
ADAM-6200 User Manual 142B.1 ASCII Commands for ADAM-6200 modulesFor users do not familiar to Modbus protocol, Advantech offers a function library as
143 ADAM-6200 User ManualAppendix B ADAM-6200 ASCII Commands$aaMName Read Module NameDescription Returns the module name from a specified module.Syn
9 ADAM-6200 User ManualChapter 1 Product Overview1.7 Certification and Safety Standard FCC – FCC 47 CFR PART 15 (Class A)– IC ICES-003 CE– EN 55011
ADAM-6200 User Manual 144$aaFName Read Firmware VersionDescription Returns the firmware version from a specified module.Syntax $aaF(cr)$ is a delimi
145 ADAM-6200 User ManualAppendix B ADAM-6200 ASCII Commands#aaVdbbbbddddddddName Write Value(s) to GCL Internal Flags (Auxiliary Flags)Description
ADAM-6200 User Manual 146$aaVdName Read GCL Internal Flags' (Auxiliary Flags) ValuesDescription This command reads all GCL internal flags'
147 ADAM-6200 User ManualAppendix B ADAM-6200 ASCII CommandsB.1.2 Analog Input Command SetFunction Description Command ExampleRead analog input from C
ADAM-6200 User Manual 148#aanName Read Analog Input from Channel NDescription Returns the input data from a specified analog input channel in a spec
149 ADAM-6200 User ManualAppendix B ADAM-6200 ASCII Commands$aa1Name Auto CalibrationDescription Calibrate the analog input range of module Syntax $a
ADAM-6200 User Manual 150$aa6Name Read Channel Enable/Disable StatusDescription Asks a specified module to return the Enable/Disable status of all a
151 ADAM-6200 User ManualAppendix B ADAM-6200 ASCII Commands$aa5mmName Set Channel Enable/Disable StatusDescription Set Enable/Disable status for al
ADAM-6200 User Manual 152#aaMHName Read Maximum ValueDescription Read the maximum values from all analog input channels in a speci-fied analog modul
153 ADAM-6200 User ManualAppendix B ADAM-6200 ASCII Commands#aaMHnName Read Maximum Value from channel NDescription Read the maximum value from a sp
ADAM-6200 User Manual 101.8 Product Label
ADAM-6200 User Manual 154#aaMLName Read Minimum ValueDescription Read the minimum values from all analog input channels in a specifiedmoduleSyntax #
155 ADAM-6200 User ManualAppendix B ADAM-6200 ASCII Commands#aaMLnName Read Minimum Value from channel NDescription Read the minimum value from a sp
ADAM-6200 User Manual 156B.1.3 Analog Input Range codeExample The command asks the specific module at address 01h to send ana-log input range code va
157 ADAM-6200 User ManualAppendix B ADAM-6200 ASCII Commands$aaCjAhsName Set Alarm ModeDescription Sets the High/Low alarm of the specified input ch
ADAM-6200 User Manual 158$aaCjAhName Read Alarm ModeDescription Returns the alarm mode for the specified channel in the specifiedADAM-6200 module.Sy
159 ADAM-6200 User ManualAppendix B ADAM-6200 ASCII Commands$aaCjAhEsName Enable/Disable AlarmDescription Enables/Disables the High/Low alarm of the
ADAM-6200 User Manual 160$aaCjChName Clear Latch AlarmDescription Sets the High/Low alarm to OFF (no alarm) for the specified inputchannel in the ad
161 ADAM-6200 User ManualAppendix B ADAM-6200 ASCII Commands$aaCjAhCCnName Set Alarm ConnectionDescription Connects the High/Low alarm of the specif
ADAM-6200 User Manual 162$aaCjRhCName Read Alarm ConnectionDescription Returns the High/Low alarm limit output connection of a specified inputchannel
163 ADAM-6200 User ManualAppendix B ADAM-6200 ASCII Commands$aaCjAhUName Set Alarm LimitDescription Sets the High/Low alarm limit value for the spec
11 ADAM-6200 User ManualChapter 1 Product Overview1.9 Front Name Plate1.10 Package InformationThe package of ADAM-6200 series module will contain the
ADAM-6200 User Manual 164$aaCjRhUName Read Alarm LimitDescription Returns the High/Low alarm limit value for the specified input channelin the addre
165 ADAM-6200 User ManualAppendix B ADAM-6200 ASCII Commands$aaCjSName Read Alarm StatusDescription Reads whether an alarm occurred to the specified
ADAM-6200 User Manual 166$aaDSccName Read AO Startup Value from One ChannelDescription Returns the startup value from a specified analog output chan
167 ADAM-6200 User ManualAppendix B ADAM-6200 ASCII Commands#aaDSccnnnnName Set AO Startup Value to One ChannelDescription Set the startup value to
ADAM-6200 User Manual 168#aaBCccnnnnName Write AO Value to One ChannelDescription Write output value to a specified analog output channel in a speci
169 ADAM-6200 User ManualAppendix B ADAM-6200 ASCII Commands$aaBEccName Read Analog Output Range Code from Channel NDescription Returns the range co
ADAM-6200 User Manual 170B.1.6 Analog Output Range codeExample The command asks the specific module at address 01h to send ana-log output range code
171 ADAM-6200 User ManualAppendix B ADAM-6200 ASCII Commands$aa6Name Read Channel StatusDescription This command requests that the specified ADAM-620
ADAM-6200 User Manual 172#aa00(data)Name Write all digital output channelsDescription This command sets all digital output channels to the specific
173 ADAM-6200 User ManualAppendix B ADAM-6200 ASCII Commands#aa1c(data)Name Write a single digital output channelDescription This command sets a sin
ADAM-6200 User Manual 12
ADAM-6200 User Manual 174$aaJCFFFFssmmName Read DI Channel Counter ValueDescription Returns the counter value from specified DI channels in a specif
Appendix CC REST for ADAM-6200
ADAM-6200 User Manual 176C.1 IntroductionREpresentational State Transfer (REST) is a design style of software architecture forWeb application behaves
177 ADAM-6200 User ManualAppendix C REST for ADAM-6200C.2.1.2 GET /analoginput/(all|{id})/rangeRequestThecontent‐typewillbe‘application/x‐www‐form
ADAM-6200 User Manual 178C.2.2 Analog OutputC.2.2.1 GET /analogoutput/(all|{id})/valueC.2.2.2 POST /analogoutput/all/valueRequestThecontent‐typewill
179 ADAM-6200 User ManualAppendix C REST for ADAM-6200C.2.2.3 GET /analogoutput/(all|{id})/rangeRequestThecontent‐typewillbe‘application/x‐www‐for
ADAM-6200 User Manual 180C.2.2.4 GET /analogoutput/(all|{id})/rangeRequestThecontent‐typewillbe‘application/x‐www‐form‐urlencoded’.{id}:istheA
181 ADAM-6200 User ManualAppendix C REST for ADAM-6200C.2.3 Digital InputC.2.3.1 GET /digitalinput/(all|{id})/valueRequestThecontent‐typewillbe‘ap
ADAM-6200 User Manual 182C.2.4 Digital OutputC.2.4.1 GET /digitaloutput/(all|{id})/valueC.2.4.2 POST /digitaloutput/all/valueRequestThecontent‐typew
183 ADAM-6200 User ManualAppendix C REST for ADAM-6200
Chapter 22 Product Specifications
www.advantech.comPlease verify specifications before quoting. This guide is intended for referencepurposes only.All product specifications are subject
ADAM-6200 User Manual iiCopyrightThe documentation and the software included with this product are copyrighted 2013by Advantech Co., Ltd. All rights a
ADAM-6200 User Manual 142.1 General SpecificationItem DescriptionEthernet 2-port 10/100 Base-TX (for Daisy chain) Protocol Modbus TCP, TCP/IP, UDP, HT
15 ADAM-6200 User ManualChapter 2 Product Specifications2.2 Analog Input Module (ADAM-6217)2.2.1 Application WiringAnalog Input DescriptionChannel 8 (
ADAM-6200 User Manual 162.2.2 Pin Assignment:2.2.3 Switch Setting
17 ADAM-6200 User ManualChapter 2 Product Specifications2.3 Analog Output Module (ADAM-6224)2.3.1 Application WiringAnalog Output DescriptionChannel 4
ADAM-6200 User Manual 182.3.2 Pin Assignment2.4 Digital Input/Output Modules (ADAM-6250/6251/6256)Digital Input DescriptionChannelADAM-6250: 8ADAM-625
19 ADAM-6200 User ManualChapter 2 Product Specifications2.4.1 Application Wiring Isolated Digital Input (6250/6251)Dry ContactWet Contact
ADAM-6200 User Manual 20 Isolated Digital OutputADAM-6250
21 ADAM-6200 User ManualChapter 2 Product SpecificationsADAM-62562.4.2 Pin Assignment ADAM-6250
ADAM-6200 User Manual 22 ADAM-6251 ADAM-6256
23 ADAM-6200 User ManualChapter 2 Product Specifications2.4.3 Switch Setting ADAM-6250 ADAM-6251
iii ADAM-6200 User Manual Declaration of ConformityCEThis product has passed the CE test for environmental specifications when shieldedcables are used
ADAM-6200 User Manual 242.5 Relay Output Modules (ADAM-6260/6266)Relay Output DescriptionChannelADAM-6260: 5 Form C and 1 Form AADAM-6266: 4 Form CCon
25 ADAM-6200 User ManualChapter 2 Product Specifications2.5.1 Application Wiring Isolated Digital InputDry ContactWet Contact
ADAM-6200 User Manual 26 Isolated Relay Output2.5.2 Pin Assignment ADAM-6260
27 ADAM-6200 User ManualChapter 2 Product Specifications ADAM-62662.5.3 Switch Setting
ADAM-6200 User Manual 28
Chapter 33 Hardware Installation
ADAM-6200 User Manual 303.1 Interface Introduction
31 ADAM-6200 User ManualChapter 3 Hardware Installation3.2 MountingADAM-6200 modules are designed as compact units and are allowed to be installedin t
ADAM-6200 User Manual 323.2.2 DIN-Rail MountingThe ADAM-6200 module can also be fixed to the cabinet by using mounting rails.You need to assemble the
33 ADAM-6200 User ManualChapter 3 Hardware Installation3.3 Wiring & ConnectionsThis section introduces basic information on wiring the power suppl
ADAM-6200 User Manual ivSafety Instructions1. Read these safety instructions carefully.2. Keep this User Manual for later reference.3. Disconnect this
ADAM-6200 User Manual 343.3.3 Daisy Chain ConnectionIn early stage of industrial automation field, most users used to deploy their automa-tion environ
35 ADAM-6200 User ManualChapter 3 Hardware InstallationNote! 1. The average latency from one module to another: 15 - 20 s:2. Typically, the maximu
ADAM-6200 User Manual 36
Chapter 44 System Configuration
ADAM-6200 User Manual 384.1 ADAM.NET Utility (software)ADAM.NET Utility, which is designed with graphical operation interface, is aimed tooffer users
39 ADAM-6200 User ManualChapter 4 System Configuration4.3 Configure ADAM-6200 with ADAM.NET UtilityAfter you've finished the connection between A
ADAM-6200 User Manual 403. Click Search Module icon in Toolbar. You will see all online modules in the left Module Tree screen and an unconfigured new
41 ADAM-6200 User ManualChapter 4 System Configuration4.3.1.1 Menua. File Open Favorite GroupYou can import the favorite configuration group file (.X
ADAM-6200 User Manual 42Case 1. If you want to upgrade your module's firmware.1. Select Firmware.2. Select I/O module3. Click Browse button to im
43 ADAM-6200 User ManualChapter 4 System ConfigurationCase 2. If you want to duplicate your module's configuration to others.(Before launching it
v ADAM-6200 User Manual ContentsChapter 1 Product Overview ...11.1 Introduction ...
ADAM-6200 User Manual 44 Terminal for Command TestingADAM-6200 series module support ASCII command and Modbus/TCP as com-munication protocol, so you
45 ADAM-6200 User ManualChapter 4 System ConfigurationDouble click the address can modify the value of coil or register: Print ScreenYou can save cur
ADAM-6200 User Manual 46 Monitor Stream/Event DataThis function will indicate real-time I/O data status of one module on your preset host computers/s
47 ADAM-6200 User ManualChapter 4 System Configuration Monitor GCL IO Data MessageThis function will indicate GCL I/O data status when it enabled.c.
ADAM-6200 User Manual 484.3.1.2 ToolbarThere are 8 graphical icons for common used options of Menu on the toolbar.Definition (from left to right)1. Op
49 ADAM-6200 User ManualChapter 4 System Configuration4.3.1.4 Main Operation ScreenMain Operation Screen located on the right side of utility includes
ADAM-6200 User Manual 504.3.2 General Configuration4.3.2.1 InformationIt indicates basic information of ADAM-6200 module.Firmware VersionIndicates the
51 ADAM-6200 User ManualChapter 4 System Configuration4.3.2.2 NetworkYou can set up required network connection on this page.Network SettingYou can se
ADAM-6200 User Manual 524.3.2.3 StreamADAM-6200 modules can actively send its data to multiple hosts periodically. It iscalled Data Stream. In this ta
53 ADAM-6200 User ManualChapter 4 System Configuration4.3.2.4 AdministrationThe administration page includes Password, reset, and restart function.Pas
ADAM-6200 User Manual viChapter 4 System Configuration... 374.1 ADAM.NET Utility (software)...
ADAM-6200 User Manual 544.3.2.5 FirmwareOn this page, you can import and export your configuration file and upgrade firm-ware.File ImportThere are fou
55 ADAM-6200 User ManualChapter 4 System Configuration4.3.2.6 Peer to Peer / EventIt will be described in following sections.4.3.2.7 Access ControlFor
ADAM-6200 User Manual 564.3.2.8 User-defined Modbus AddressIn order to provide user with more flexible and scalable in deploying ADAM module,ADAM-6200
57 ADAM-6200 User ManualChapter 4 System Configuration4.3.3 I/O ConfigurationAfter the introduction of ADAM-6200 general configuration in previous sec
ADAM-6200 User Manual 584.3.3.1 ADAM-6217 Analog Input Channel OverviewLocateIt can help user search ADAM module with light sign. (Status LED will be
59 ADAM-6200 User ManualChapter 4 System ConfigurationInput RangeYou can select input channel and its voltage/current range and click Apply button tot
ADAM-6200 User Manual 60Channel Information– OverviewIt presents which channel is enabled and its current input value.– Average settingYou can decide
61 ADAM-6200 User ManualChapter 4 System ConfigurationAlarm SettingWhen the analog input value is higher than the high alarm value, or lower than thel
ADAM-6200 User Manual 624.3.3.2 ADAM-6224 Digital Input Channel OverviewLocateIt can help user search ADAM module with light sign. (Status LED will b
63 ADAM-6200 User ManualChapter 4 System ConfigurationInvert signalIt will invert the logic state of input signal. In another words, when no signal pu
Chapter 11 Product Overview
ADAM-6200 User Manual 64CalibrationIt's for sure that each module is well calibrated when it's in manufacturing process.However, in certain
65 ADAM-6200 User ManualChapter 4 System Configuration2. Trim Span - It's used to help user calibrate the high limit of output range by entering
ADAM-6200 User Manual 664.3.3.3 ADAM-6250 Digital Input Channel OverviewLocateIt can help user search ADAM module with light sign. (Status LED will b
67 ADAM-6200 User ManualChapter 4 System ConfigurationAdvanced channel setting1. DI configurationIn ADAM-6250 advanced channel setting, you can config
ADAM-6200 User Manual 68Counter modeWhen you choose Counter mode, one counter will count the pulse number of the dig-ital signal from the selected cha
69 ADAM-6200 User ManualChapter 4 System ConfigurationLow to High Latch modeWhen you choose Low to High Latch mode, once the digital input channel det
ADAM-6200 User Manual 70High to Low Latch modeWhen you choose High to Low Latch mode, once the digital input channel detectslogic level changes from h
71 ADAM-6200 User ManualChapter 4 System ConfigurationFrequency modeWhen you choose Frequency mode, ADAM-6200 digital module will calculate the fre-qu
ADAM-6200 User Manual 72DO modeWhen you choose DO mode, you can control the digital output value of the selectedchannel by the DO button. The current
73 ADAM-6200 User ManualChapter 4 System ConfigurationPulse Output modeThe pulse output is the same as PWR. After you choose the Pulse output mode, th
ADAM-6200 User Manual 21.1 IntroductionThe ADAM-6200 series is a new ADAM Ethernet I/O family and includes analog I/O,digital I/O and relay modules. N
ADAM-6200 User Manual 74Low to high delayIt means there will be certain time delay when the output value changes from logiclow to logic high as below.
75 ADAM-6200 User ManualChapter 4 System ConfigurationHigh to low delayIt means there will be certain time delay when the output value changes from lo
ADAM-6200 User Manual 764.3.3.4 ADAM-6251 Digital Input Channel OverviewLocateIt can help user search ADAM module with light sign. (Status LED will b
77 ADAM-6200 User ManualChapter 4 System Configuration4.3.3.5 ADAM-6256 Digital Output Channel OverviewLocateIt can help user search ADAM module with
ADAM-6200 User Manual 784.3.3.6 ADAM-6260 Digital Output Channel OverviewLocateIt can help user search ADAM module with light sign. (Status LED will
79 ADAM-6200 User ManualChapter 4 System Configuration4.3.3.7 ADAM-6266 Digital Output Channel OverviewLocateIt can help user search ADAM module with
ADAM-6200 User Manual 804.3.4 Peer to PeerWhen you want to send a signal from one module to another module, Peer-to-Peer isa perfect solution. With Pe
81 ADAM-6200 User ManualChapter 4 System Configuration1. Period Time Function:The value of the input channel will be updated to the target devices wit
ADAM-6200 User Manual 82Basic Mode ConfigurationThe Status Display of basic mode is shown above. You can define the target deviceby entering its IP ad
83 ADAM-6200 User ManualChapter 4 System Configuration4.3.4.2 Advanced ModeIn advanced mode, there will be multiple target devices to receive the data
3 ADAM-6200 User ManualChapter 1 Product Overview1.2 Feature Highlights1.2.1 Easier Installation and Deployment Daisy Chain connection with auto-bypa
ADAM-6200 User Manual 84Advanced Mode ConfigurationWhen you choose the advanced mode, the Main Operation screen area is shown asabove. With advanced m
85 ADAM-6200 User ManualChapter 4 System ConfigurationChoose the channel which provides the setting for other channels by the Channelcombo box at the
ADAM-6200 User Manual 86With GCL enabled, a computer (or a controller) can be removed from the con-trol system since the ADAM-6200 modules can play as
87 ADAM-6200 User ManualChapter 4 System Configuration4.3.5.2 Configuration EnvironmentAs previously mentioned, when you try to spread one of ADAM-620
ADAM-6200 User Manual 88The top icon definition in GCL Menu:Logic rule configuration:There are 16 logic rules available on one ADAM-6200 module, so yo
89 ADAM-6200 User ManualChapter 4 System Configuration4.3.5.3 Basic Logic rule programming Input Condition stageThe Input Condition stage is a logic
ADAM-6200 User Manual 90Mode Description ConditionNo Operation No operation N/AAI Local AI channel value >, =, <DI Local DI channel value True,
91 ADAM-6200 User ManualChapter 4 System ConfigurationLocal Analog Input Channel (AI)1. After you choose AI as input mode, select the channel by the C
ADAM-6200 User Manual 92ADAM-6200 analog input module features Scaling function to convert the voltage (orcurrent) value to the engineer unit value. F
93 ADAM-6200 User ManualChapter 4 System ConfigurationInternal Flag (AuxFlag)There are 16 internal flags on one ADAM-6200 module. The data type of int