Synergy Nano Technical Manual, Revision -
Page 235
14.2 Configuring Cascade Software
14.2.1 General
Several settings and parameter options should be configured before using Cascade software. T
his is
especially important when you are switching between single loop control and cascade control. In addition
your PIDs will usually require additional tuning, especially with the Cascade Proportional Band setting. The
PID / Parameter Option Chart below shows the recommended and default settings for Cascade algorithm.
PID / Parameter Option Chart
PID Parameter Recommended Default
Cascade Enabled Enabled Disabled
Cascade Sensor Select As required 120, RTD2
Cascade High Limit (Temp) 200 200
Cascade Low Limit (Temp) -100 -100
Cascade Proportional Band 7.0 7.0
Cascade Reset 0.02 0.02
Cascade Rate 0.00 0.00
Cascade Rate Band 0.00 0.00
Heat Proportional Band 14.0 7.0
Cool Proportional Band 10.0 5.0
In order to view and change the Cascade PID / Parameter settings, press the SETUP Screen Navigation key
and go to the screen below. For Inner Loop settings, go to the PID Settings\PID Ch1\Heat or Cool folder.
Cascade Setup Folder
PID Folder: Cascade PID loop settings.
(Sect. 3.2)
Settings Folder: High and Low Air
Temperature Limits and the Sensor
Selection.
Enabled Folder: Enable and disable the
cascade feature.