Drier Device
This output controls the Air Drier for dehumidification.
Output is either Time Proportioning or On/Off
L11 Dehumidify On Percent dehumidify required to enable dehumidify device
L12 Dehumidify Off Percent humidity required to turn off dehumidify device
LEV 1 Selects whether to use the Dehumidify Coil or the Drier
Device (Drier requires the Input 2 to be open)
Dehumidify Coil vs. Drier Logic (Input 2) When closed selects using the Dehumidify Coil. When
open, and when LEV 1 is set to Use Drier, it will disable
the dehumidify coil and use the Drier device instead.
Affected By: Default Value: Range:
Channel 2 Proportional Band Cooling 40 0 - 50 Degrees C
Reset for Channel 2 Cooling 0.1 0 - 9.9 Repeats/minute
Rate for Channel 2 Cooling 0 0 - 9.9 Minutes
Cycle Time for Channel 2 Cooling 7 1 - 60 Seconds
Rate Band for Channel 2 Cooling 0 0 - 7 Seconds
Wick Pan
This output is on whenever channel 2 is on.