Page 65
PID Heat
Time Proportioning output that controls the heaters.
Output is Time Proportioning
Affected By: Default Value: Range:
Channel 1 Proportional Band 7 0 - 50 Degrees C
Reset for Channel 1 Heating 0.02 0 - 9.9 Repeats/minute
Rate for Channel 1 Heating 0 0 - 9.9 Minutes
Cycle Time for Channel 1 Heating 5 1 - 60 Seconds
Rate Band for Channel 1 Heating 0 0 - 7 Seconds
PID Cool
This is a time proportioning output that energizes the cool solenoid permitting refrigerant flow to the
Evaporator Coil.
Output is Time Proportioning
Affected By: Default Value: Range:
Channel 1 Proportional Band 7 0 - 50 Degrees C
Reset for Channel 1 Cooling 0.02 0 - 9.9 Repeats/minute
Rate for Channel 1 Cooling 0 0 - 9.9 Minutes
Cycle Time for Channel 1 Cooling 5 1 - 60 Seconds
Rate Band for Channel 1 Cooling 0 0 - 7 Seconds