Synergy Nano Technical Manual, Revision -
Page 284
17.4.10 Low Resolution Sensor Wiring
The refrigeration pressure transducers should be connected to P4 as follows (see P4 in the Olympic Board
photo below): A typical transducer configuration for a cascade refrigeration system is listed in the table
below. Note that the Low Resolution inputs are not limited to pressure measurement and can be used for
any transducer compatible with the 5VDC full scale or 4-20 mA signal conditioners.
Sensor Function Range Voltage Range Connection COM
Low stage, Discharge Pressure 0-600PSI 0-5 VDC P4-pin 1 P4- Pin 10
Low stage, Suction Pressure 0-200PSI 0-5 VDC P4-pin 2 P4- Pin 10
Low stage, Oil Pressure 0-200PSI 0-5 VDC P4-pin 3 P4- Pin 10
High stage, Discharge Pressure 0-600PSI 0-5 VDC P4-pin 4 P4- Pin 10
High stage, Suction Pressure 0-200PSI 0-5 VDC P4-pin 5 P4- Pin 10
High stage, Oil Pressure 0-200PSI 0-5 VDC P4-pin 6 P4- Pin 10
Pressure scaling is setup in the Low Res Input Calibration Setup screen as shown below:
Example 1
In this example the low stage compressor
discharge pressure is monitored on Input 1. The
high engineering scale is set to 600 for 600 PSI.
Example 2
In this example the low stage compressor suction
pressure is monitored on Input 2. The high
engineering scale is set to 200 for 200 PSI.
The Low Resolution inputs can be viewed in the Events/Low Res screen. These inputs can be used as the
input for a programmable alarm
in addition to be used as the sensor for a control channel.