Synergy Nano Technical Manual, Revision -
Page 41
Raw Calibration
This screen is used to enter an offset and
gain for the input voltage. This calibration
can be used to compensate for a
difference in the reading due to Olympic
board tolerance, sensor error, etc.
Select the Gain or Offset text box to open
the number pad and enter the value, then
press Accept.
The Current Reading field displays the
Voltage with the current values of Gain
and Offset applied. The Gain and Offset
values are discarded if Cancel is pressed
and saved if Apply is pressed.
Voltage Scale
High and Low Voltage Scale parameters
provided the flexibility to use 0-5VDC, 4-
20mA or other sensor output ranges.
Set the High Voltage Scale to the full scale
output of the sensor
.
Set the Low Voltage Scale to the Zero
scale output of the sensor
.
Highlight the parameter and Pres the
Change button to adjust these parameters.
Engineering Scale
High and Low Engineering Scale
parameters provide the flexibility to scale
the sensor data to engineering units.
Set the High Engineering Scale to the full
scale output of the sensor
.
Set the Low Engineering Scale to the Zero
scale output of the sensor
.
Highlight the parameter and press the
Change button to adjust these parameters.
For Example, for a Vaisala sensor set the
Low Scale to 0 and the High Scale to
100%. For altitude applications, the High
Engineering Scale is typically 1000 Torr.